Figure 1. Testing Circuit Breakers.
MAINTENANCE INSTRUCTIONS FOR CIRCUIT BREAKERS

Aviation Maintenance Manual For Power Train Shop P/N 1036459 And P/N Sc492097Cla65
Page Navigation
  210    211    212    213    214  215  216    217    218    219    220  
img
TM 1-4920-438-13&P
0055 00
REMOVAL
WARNING
HIGH VOLTAGE exists in electrical system of shop. All electrical inspections, repairs, or
replacements will be performed with power OFF and only by a qualiied electrician. Serious
shock hazards exist which could result in INJURY OR EVEN DEATH to personnel.
Figure 2.
Replacing Circuit Breakers.
1.
Move all circuit breakers to OFF position and tag.
2.
Mark and disconnect wires from circuit breaker that will be removed.
NOTE
Do not completely remove screw; loosen only enough to allow removal of circuit breaker.
3.
Loosen screw securing circuit breaker.
4.
Pull circuit breaker from bus bar and remove from circuit breaker box.
0055 00-3