TM 10-5411-236-13&P
UNIT MAINTENANCE
AUTHORIZED STOCKAGE LIST MOBILITY SYSTEM (ASLMS)
MODEL NUMBER FPU-8/12 PARTS (OD) P/N 15005002-001
MODEL NUMBER FPU-8/12 PARTS (DS) P/N 15005002-002
MODEL NUMBER FPU-8/12 BULK (OD) P/N 15005001-001
MODEL NUMBER FPU-8/12 BULK (DS) P/N 15005001-002
A/C
INSPECT
INITIAL SETUP:
Material/Parts
References
Personnel Required
One
Equipment Condition
ASLMS set-up. Disconnected from
PDISE. Main Breaker set to OFF position.
Tools
General Mechanic's Tool Kit (Item 4, WP 0063 00)
INSPECT
WARNING
Electrical power must be disconnected before any electrical system work is performed to
prevent electrical shock, injury, or death (electrocution). Only trained and qualified
personnel (MOS 51R, 52C, 52E, or 52G) may perform maintenance or attempt to correct
electrical discrepancies on the electrical system.
1. Verify electrical (AC) connection (1) from the M40 PDISE (2) to the entrance panel of the FPU-12 (3).
2. Verify electrical (AC) connection of the FPU-8 (4) from the FPU-12 container.
3. Use a multi-meter to check the GFCI electrical outlets in the FPU-12 container.
4. Depress the GFCI test button to check ground fault circuit isolation.
5. Depress the reset button to reactivate the outlet power.
6. Repeat steps 4 and 5 for each GFCI electrical outlet.
0040 00-1