TM 9-4933-223-13&P
3-8.
TROUBLESHOOTING INFORMATION (cont)
Table 3-1. Troubleshooting (cont)
MALFUNCTION
TEST OR INSPECTION
LOCATION
CORRECTIVE ACTION
CABLE ADAPTER ASSEMBLY
3. ENVIRONMENTAL CONTROL UNITS OR EXHAUST FANS DO NOT OPERATE
CORRECTLY.
Step 1. Check that power source is connected according to instruc-
With power source off, make cable connections speci-
fied on warning plate.
Step 2. Check cable adapter assembly for open circuits.
With power source off, disconnect cable adapter
assembly from the power source and make an
ohmmeter check of each phase through the cable
from pin end to socket end. Repair as required (p 3-213).
120/208V CABLE ASSEMBLY
4. ENVIRONMENTAL CONTROL UNITS OR EXHAUST FANS DO NOT OPERATE
CORRECTLY.
Step 1. Check that electrical power to the shelter is connected
according to instructions on the warning plate
With power source off, make cable connections speci-
fied by warning plate.
3-8