in the scuba tanks as they are being charged.
4-7.
OPERATION INSTRUCTIONS.
4-8.
PRIOR TO OPERATION Prior to operating the
service units, perform the following procedure.
a.
Transport the unit to work site and select as
level an area as possible to park the Service Units. Set
hand brakes and stabilizing jack.
High pressure gas Is dangerous Check all
tubing and service hoses for damage,
cracks or deterioration
b.
Perform all inspection, checks, and
services required Refer to Table 5-1
Under no circumstances should the air or
oxygen
purification
cartridges
in
the
purification cylinders (7, 8, Figure 7-1) be
allowed
to
become
contaminated
with
moisture If in doubt, change the cartridges
Under no circumstances will cartridges be
interchanged between the air or oxygen
purified cylinders on a Type II system
NOTE
When air or oxygen purification cartridges are changed,
make certain to record the time the change was made
Approximate time lapse for cartridge change is 8 hours
Actual frequency of cartridge change depends on
governing weather conditions at a given time or place,
and the condition of the compressed gas (air or oxygen)
being used
c.
Check the number of hours that the
cartridges in the purifying cylinders have been used If the
next period of operation will exceed the remaining useful
life of the cartridges, replace the cartridges
4-9.
TYPE I (AIR) - CHARGING THE TYPE I (AIR)
SERVICING UNIT (See Figure 4-3 )
The stems and seats of the control panel
valves may be damaged by overtightening
All valves should be tightened enough to
prevent leakage.
a.
Prior to attaching the service hose to the
servicing unit, make sure all valves are closed, including
drain valves
b.
Attach a source of clean, dry, breathable air
to recharge connection (9) on control panel.
The stems and seats of the control panel
valves may be damaged by overtightening
All valves should be tightened enough to
prevent leakage.
c. Close manifold shut-off valves (10), open
cylinder valves (2) on gas cylinders (1) to be charged
and place cam lever valve (5) m the up position Open
recharge valve (8).
d.
Service air cylinder (1) to a maximum 3200
psi for breathable air (Type I).
e.
Close recharge valve (8)
Do NOT disconnect service hose until
service hose line has been bled of all
pressure
f.
Open service hose bleed valve located on
the source furnishing the breathable air.
g.
Disconnect service hose.
h.
Connect yoke adaptor (21) to scuba tanks
i.
Be sure scuba manifold bleed of valve (18)
is closed
j.
Open manifold shut-off valve (10)
k.
Adjust regulator (12) to desired pressure
I.
Open scuba manifold servicing valve (14)
and scuba manifold charging valve (19)
4-5