TM 1-4920-438-13&P
0032 00
DISCONNECTING PDB FROM GENERATOR (IF NECESSARY)
WARNING
This procedure is required only if a complete power shutdown is necessary. Only a qualiied
electrician shall to disconnect PDB from generator. Serious shock hazards exist which could
result in INJURY OR EVEN DEATH to personnel.
Figure 5.
Disconnecting PDB from Generator.
1.
Ensure all circuit breakers on PDB (Figure 5) are in the OFF position.
2.
Disconnect black wire from lug L1, red wire from lug L2, blue or orange wire from lug L3, and white and green
wires from lug L0 on generator (Figure 5).
3.
Disconnect pigtail from PDB.
0032 00-5