TM 1-4920-500-13&P
0025 00
1
4
3
2
SSAE135
INSPECT
1. Inspect eyewash station bracket (1) for loose bolts (2).
2. If necessary, torque bolts (2) 160-190 in. lbs.
3. If bolts (2) will not tighten to specified torque follow procedures in WP 0038 00.
4. Inspect eyewash station assembly for damage that will deem eyewash station assembly non-operational.
5. Replace eyewash station assembly if deemed non-operational.
REPLACE
1. Remove eyewash station from eyewash station bracket (1).
2. Remove two bolts (2), two lock washers (3), two flat washers (4), and eyewash station bracket (1).
3. Position new eyewash station bracket (1) by aligning bolt holes with wall inserts.
4. Install two bolts (2), two lock washers (3), and two flat washers (4).
5. Torque bolts (2) 160-190 in. lbs.
End of Work Package