60 AMP RECEPTACLE
3
2
1
4
SSAE157
Inspect
Ensure 60 amp receptacle (2) connections are not loose or damaged.
Test
1. Move main circuit breaker to OFF position.
2. Test 60 amp receptacle (2) and wires for continuity.
3. Replace 60 amp receptacle (2) if a problem is detected.
4. Move main circuit breaker to ON position.
Replace
WARNING
HIGH VOLTAGE exists in electrical system of shop. All electrical inspections,
repairs, or replacements will be performed with power OFF and only by a
qualified electrician. Serious shock hazards exist which could result in INJURY
OR EVEN DEATH to personnel.
1. Move main circuit breaker to OFF position.
2. Remove four machine screws (1) attaching 60 amp receptacle (2) to 54 degree angle adapter (3).
3. Pull 60 AMP receptacle (2) out of 54 degree angle adapter (3) until wire lug terminals (4) are exposed.
4. Loosen wire lug terminals (4) and remove wires.
5. Obtain new 60 amp receptacle (2).
NOTE
Receptacle lugs are identified by letters "X", "Y", and "Z" with ground connection
being identified by color green. Black wire will be attached to "X", red wire will be
attached to "Y", and blue wire will be attached to "Z".
6. Install new 60 amp receptacle (2) by reattaching wires to wire lug terminals (4).
7. Push 60 amp receptacle (2) back into 54 degree angle adapter (3).
8. Install four machine screws (1) reattaching 60 amp receptacle (2) to 54 degree angle adapter (3).
9. Move main circuit breaker to ON position.