• Home
  • Download PDF
  • Order CD-ROM
  • Order in Print
'Microsoft Word - WP1' by ginda.roadruck - Page 213 of 338
'Microsoft Word - WP1' by ginda.roadruck - Page 215 of 338

Operator And Field Maintenance For Armament And Electrical Shop P/N 1024506
Page Navigation
  193    194    195    196    197  198  199    200    201    202    203  
img
.
TM 1-4920-500-13&P
0034 00
60 AMP RECEPTACLE
3
2
1
4
SSAE157
Inspect
Ensure 60 amp receptacle (2) connections are not loose or damaged.
Test
1. Move main circuit breaker to OFF position.
2. Test 60 amp receptacle (2) and wires for continuity.
3. Replace 60 amp receptacle (2) if a problem is detected.
4. Move main circuit breaker to ON position.
Replace
WARNING
HIGH VOLTAGE exists in electrical system of shop. All electrical inspections,
repairs, or replacements will be performed with power OFF and only by a
qualified electrician. Serious shock hazards exist which could result in INJURY
OR EVEN DEATH to personnel.
1. Move main circuit breaker to OFF position.
2. Remove four machine screws (1) attaching 60 amp receptacle (2) to 54 degree angle adapter (3).
3. Pull 60 AMP receptacle (2) out of 54 degree angle adapter (3) until wire lug terminals (4) are exposed.
4. Loosen wire lug terminals (4) and remove wires.
5. Obtain new 60 amp receptacle (2).
NOTE
Receptacle lugs are identified by letters "X", "Y", and "Z" with ground connection
being identified by color green. Black wire will be attached to "X", red wire will be
attached to "Y", and blue wire will be attached to "Z".
6. Install new 60 amp receptacle (2) by reattaching wires to wire lug terminals (4).
7. Push 60 amp receptacle (2) back into 54 degree angle adapter (3).
8. Install four machine screws (1) reattaching 60 amp receptacle (2) to 54 degree angle adapter (3).
9. Move main circuit breaker to ON position.
0034 00-2


Privacy Statement
Press Release
Contact

© Copyright Integrated Publishing, Inc.. All Rights Reserved.