0058 00
TM 1-4920-435-13&P
TEST AND INSPECTION
60 AMP RECEPTACLE
1.
Move main circuit breaker to OFF position.
2.
Test 60 amp receptacle (Figure 1, Item 2) and wires for continuity.
3.
Replace 60 amp power receptacle (Figure 1, Item 2) if problems are detected.
4.
Move main circuit breaker to ON position.
REMOVAL
60 AMP RECEPTACLE
WARNING
HIGH VOLTAGE exists in electrical system of shop. All electrical inspections, repairs, or
replacements will be performed with power OFF and only by a qualiied electrician. Serious
shock hazards exist which could result in INJURY OR EVEN DEATH to personnel.
1.
Move main circuit breaker to the OFF position.
2.
Remove four machine screws (Figure 1, Item 1) attaching 60 amp receptacle (Figure 1, Item 2) to 45 degree
angle adapter (Figure 1, Item 3).
3.
Pull 60 amp receptacle (Figure 1, Item 2) out of 45 degree angle adapter (Figure 1, Item 3) until wire lug
terminals (Figure 1, Item 1) are exposed.
4.
Loosen wire lug terminals (Figure 1, Item 4) and remove wires.
INSTALLATION
60 AMP RECEPTACLE
1.
Move main circuit breaker to the OFF position.
NOTE
Receptacle lugs are identiied by letters "X", "Y", and "Z" with ground connections being identi-
ied by color green. Black wire will be attached to "X", red wire will be attached to "Y", and blue
wire will be attached to "Z".
2.
Install 60 amp receptacle (Figure 1, Item 2) by reattaching wires to wire lug terminals (Figure 1, Item 1).
3.
Push 60 amp receptacle (Figure 1, Item 2) into 45 degree angle adapter (Figure 1, Item 3).
4.
Install four machine screws (Figure 1, Item 1) attaching 60 amp receptacle (Figure 1, Item 2) to 45 degree
angle adapter (Figure 1, Item 3).
5.
Move main circuit breaker to ON position.
0058 00-2